Wire Size Calculator (AWG)
Find the smallest copper or aluminum conductor that can carry your load current, based on the NEC 310.16 ampacity table.
🔒 Saved only in your browser — these results never leave your device.
How to use this calculator
- Enter your load current in amps.
- Choose the conductor metal — copper or aluminum.
- Pick the insulation temperature rating (60/75/90°C) marked on the cable.
- Click Find wire size to get the smallest AWG whose ampacity covers your load.
How wire sizing works
Each conductor size has a maximum continuous current (its ampacity) that depends on the metal and the temperature rating of the insulation. This calculator returns the smallest standard size whose ampacity is at least your load current, using the widely used NEC Table 310.16 values for conductors in a raceway at an ambient temperature of 30°C.
AWG size, mm² and copper ampacity
Quick reference for copper conductors (75°C column):
| AWG | mm² (approx) | Ampacity 75°C |
|---|---|---|
| 14 | 2.1 | 20 A |
| 12 | 3.3 | 25 A |
| 10 | 5.3 | 35 A |
| 8 | 8.4 | 50 A |
| 6 | 13.3 | 65 A |
| 4 | 21.2 | 85 A |
| 2 | 33.6 | 115 A |
| 1/0 | 53.5 | 150 A |
| 2/0 | 67.4 | 175 A |
| 4/0 | 107.2 | 230 A |
Important factors not included here
- Small-conductor rule (NEC 240.4(D)): overcurrent protection is generally limited to 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
- Continuous loads must be sized at 125% of the load current.
- Voltage drop, ambient temperature and conductor bundling can require a larger size.
Always confirm with the current code edition and a licensed electrician.
Frequently asked questions
- What size wire do I need for 20 amps?
- 12 AWG copper is the usual choice for a 20 A circuit; use 14 AWG for 15 A and 10 AWG for 30 A, following the NEC 240.4(D) small-conductor limits.
- Is a higher AWG number thicker or thinner?
- Thinner. AWG runs backwards — a smaller number is a thicker wire (6 AWG is much thicker than 14 AWG).
- Does aluminum need a bigger size than copper?
- Yes. Aluminum carries less current for the same size, so it usually needs to be one to two AWG sizes larger than copper for the same load.
- What does the temperature rating mean?
- It is the maximum temperature the insulation can withstand (60/75/90°C). A higher rating allows slightly more ampacity, but terminations are often limited to the 60°C or 75°C column.
More calculators
📉 Voltage Drop
Voltage drop and % drop for a cable run.
🔁 Watts / Volts / Amps
Convert between W, V and A for DC and AC.
⚙️ Three-Phase Power
kW, kVA, amps and power factor.
🧰 Conduit Fill
Minimum EMT/PVC/RMC size per NEC.
All calculators
Basics & Ohm's law
Resistors & capacitors
- 🎨 Resistor Color Code
- 🔠 SMD Resistor Code
- 🔢 Capacitor Code
- 💡 LED Resistor
- 🔌 Series / Parallel Resistors
- 🔋 Series / Parallel Capacitors
Power, wiring & mains
- 📉 Voltage Drop
- 🧵 Wire Size (AWG)
- ⚙️ Three-Phase Power
- 📐 Power Factor Correction
- 🔌 Energy Cost
- 🔁 kVA / kW / Amps
- 🔌 Transformer Sizing
- 🌀 Motor Full-Load Current
- 🧰 Conduit Fill
- 📊 Main Panel Capacity