电机满载电流计算器
免费电机满载电流计算器,输入值直接在您的设备上计算。
Technical references: Schneider Electric motor-current formulas. The calculated current is an engineering estimate. Nameplate current and the code table required by the local authority take priority; the 125% value is not a breaker or overload setting. NFPA NEC Article 430 development record.
🔒 结果只保存在当前浏览器内,不会离开您的设备。
How to use this calculator
- Choose single-phase or three-phase.
- Enter the rated power (HP or kW).
- Enter the voltage, efficiency (%) and power factor from the nameplate.
- Click Calculate for the full-load current plus the 125% conductor-sizing value.
Full-load current formula
Because a motor has losses (efficiency η) and reactive draw (power factor PF), the input current at rated output is — three-phase: I = (HP × 746) / (√3 × V × η × PF); single-phase: I = (HP × 746) / (V × η × PF). For a kW rating, replace HP × 746 with kW × 1000. One horsepower equals 746 W of mechanical output and η is entered as a fraction (90% → 0.90).
Quick reference: HP to full-load amps (3Ø, 400 V)
Estimated at η 0.9 and PF 0.85 — confirm against the motor nameplate:
| Motor | FLA | Motor | FLA |
|---|---|---|---|
| 1 HP | 1.4 A | 15 HP | 21.1 A |
| 2 HP | 2.8 A | 20 HP | 28.2 A |
| 3 HP | 4.2 A | 25 HP | 35.2 A |
| 5 HP | 7.0 A | 30 HP | 42.2 A |
| 7.5 HP | 10.6 A | 40 HP | 56.3 A |
| 10 HP | 14.1 A | 50 HP | 70.4 A |
Why the 125% value matters
For a single continuous-duty motor, the NEC (Article 430) requires branch-circuit conductors to be rated at least 125% of the full-load current. For final NEC sizing, code generally requires the table values in 430.248/430.250 rather than a calculated figure — use this result for estimating and confirm against the table and nameplate.
常见问题
- How many amps does a 10 HP three-phase motor draw?
- At 400 V with efficiency 0.9 and PF 0.85, about 14 A. Always confirm against the motor's nameplate full-load current.
- Why size conductors at 125%?
- The NEC requires branch-circuit conductors and overload protection for a continuous-duty motor to be rated at least 125% of the full-load current.
- Should I use the calculated value or the NEC table?
- Use this calculation for estimating. For code compliance, the NEC generally requires the table values in 430.248 (single-phase) or 430.250 (three-phase).
更多计算器
⚙️ 三相电功率计算器
快速计算三相电功率计算器。
📉 电压降计算器
快速计算电压降计算器。
🧵 电线线径计算器(AWG・mm²)
快速计算电线线径计算器(AWG・mm²)。
🔁 kVA、kW、安培换算
快速计算kVA、kW、安培换算。
全部计算器
基础与欧姆定律
电阻与电容
电力、配线与电源
- 📉 电压降计算器
- 🧵 电线线径计算器(AWG・mm²)
- ⚙️ 三相电功率计算器
- 📐 功率因数校正电容计算
- 🔌 电费计算器
- 🔁 kVA、kW、安培换算
- 🔌 变压器容量计算器
- 🌀 电机满载电流计算器
- 🧰 导管填充率计算器
- 📊 配电箱容量计算