Technical reference: Schneider Electric power and power-factor guidance. Results assume sinusoidal voltage/current and a balanced three-phase load. Measure phase imbalance and harmonics separately.
🔒 결과는 이 브라우저에만 저장되며 기기 밖으로 전송되지 않습니다.
How to use this calculator
- Choose what you know: voltage & current or voltage & power (kW).
- Enter the line-to-line voltage (e.g. 400 V) — the voltage measured between any two phases.
- Enter the line current in amps, or the real power in kW.
- Enter the power factor (0–1): about 0.9 for motors at full load, 1.0 for purely resistive loads.
- Read the current, real power (kW), apparent power (kVA) and reactive power (kVAR).
Three-phase power formulas
For a balanced three-phase load using the line-to-line voltage VL:
The same line-quantity formula works for both star (wye) and delta connections, because √3 already accounts for the phase-to-line relationship. Using phase quantities instead: P = 3 × Vphase × Iphase × PF.
Symbols and units
| Symbol | Meaning | Unit |
|---|---|---|
| VL | Line-to-line voltage | volts (V) |
| I | Line current | amps (A) |
| P | Real (active) power | kilowatts (kW) |
| S | Apparent power | kilovolt-amps (kVA) |
| Q | Reactive power | kVAR |
| PF | Power factor = P / S | 0 to 1 |
Quick reference: amps to kW at 400 V (three-phase)
How many kW a balanced three-phase load draws at 400 V:
| Current | kW at PF 0.8 | kW at PF 1.0 |
|---|---|---|
| 10 A | 5.5 | 6.9 |
| 16 A | 8.9 | 11.1 |
| 20 A | 11.1 | 13.9 |
| 25 A | 13.9 | 17.3 |
| 32 A | 17.7 | 22.2 |
| 40 A | 22.2 | 27.7 |
| 50 A | 27.7 | 34.6 |
| 63 A | 34.9 | 43.6 |
| 80 A | 44.3 | 55.4 |
| 100 A | 55.4 | 69.3 |
| 125 A | 69.3 | 86.6 |
| 160 A | 88.7 | 110.9 |
For 415 V multiply by 1.04; for 380 V multiply by 0.95.
자주 묻는 질문
- What is the difference between kW and kVA?
- kW is real power (the part that does useful work); kVA is apparent power (the total the supply must deliver). They are linked by the power factor: kW = kVA × PF, and are equal only when PF = 1.
- How many kW is 100 A at 400 V three-phase?
- At PF 1.0 it is √3 × 400 × 100 ÷ 1000 ≈ 69.3 kW; at PF 0.8 it is about 55.4 kW.
- What power factor should I use?
- About 0.85–0.9 for induction motors at full load, lower for lightly loaded motors, and 1.0 for purely resistive loads such as heaters.
- Do I use line or phase voltage?
- Use the line-to-line voltage (e.g. 400 V) with the √3 formulas above. The √3 factor already converts between phase and line values for a balanced load.
관련 계산기
🔁 kVA·kW·암페어 변환기
kVA·kW·암페어 변환기을(를) 빠르게 계산합니다.
📐 역률 보상 콘덴서 계산기
역률 보상 콘덴서 계산기을(를) 빠르게 계산합니다.
🌀 모터 전부하 전류 계산기
모터 전부하 전류 계산기을(를) 빠르게 계산합니다.
🧵 전선 굵기 계산기(AWG·mm²)
전선 굵기 계산기(AWG·mm²)을(를) 빠르게 계산합니다.
모든 계산기
기초·옴의 법칙
저항·커패시터
전력·배선·전원
- 📉 전압 강하 계산기
- 🧵 전선 굵기 계산기(AWG·mm²)
- ⚙️ 3상 전력 계산기
- 📐 역률 보상 콘덴서 계산기
- 🔌 전기 요금 계산기
- 🔁 kVA·kW·암페어 변환기
- 🔌 변압기 용량 계산기
- 🌀 모터 전부하 전류 계산기
- 🧰 전선관 충전율 계산기
- 📊 분전반 용량 계산기