How to use this calculator
- Enter the heat pump's heat output in kW (the thermal power it delivers).
- Enter the COP — how many units of heat it gives per unit of electricity.
- Pick the supply and click Calculate load for the electrical input, current and breaker.
How the electrical load is found
A heat pump's electrical input is its heat output divided by the COP; current also depends on supply and power factor:
Pelec = heat ÷ COP · I = Pelec ÷ (230 × PF) (1-phase) or Pelec ÷ (√3 × 400 × PF) (3-phase)
The suggested breaker is the next standard rating above the running current. Heat pumps draw a higher inrush at start-up, so the manufacturer may specify a larger breaker or a soft starter.
Typical COP and what it means
| COP | Heat per kW of electricity |
|---|---|
| 2.5 | 2.5 kW |
| 3.5 | 3.5 kW |
| 4.5 | 4.5 kW |
COP falls in cold weather, so a unit rated COP 4 in mild conditions may give 2–2.5 at −10 °C, raising the electrical load.
常見問題
- How much electricity does a heat pump use?
- Divide the heat output by the COP. A 6 kW heat pump at COP 3.5 draws about 1.7 kW of electricity — roughly 7.5 A on a 230 V supply.
- What breaker does a heat pump need?
- Size it above the running current, but follow the data plate: inrush at start-up and defrost cycles often mean the maker specifies a larger breaker or a dedicated circuit.
- Why does the load change with temperature?
- COP drops as the outdoor temperature falls, so the same heat output needs more electrical input on the coldest days — exactly when demand is highest.