How to use this calculator
- Enter the heat pump's heat output in kW (the thermal power it delivers).
- Enter the COP — how many units of heat it gives per unit of electricity.
- Pick the supply and click Calculate load for the electrical input, current and breaker.
How the electrical load is found
A heat pump's electrical input is its heat output divided by the COP; current also depends on supply and power factor:
Pelec = heat ÷ COP · I = Pelec ÷ (230 × PF) (1-phase) or Pelec ÷ (√3 × 400 × PF) (3-phase)
The suggested breaker is the next standard rating above the running current. Heat pumps draw a higher inrush at start-up, so the manufacturer may specify a larger breaker or a soft starter.
Typical COP and what it means
| COP | Heat per kW of electricity |
|---|---|
| 2.5 | 2.5 kW |
| 3.5 | 3.5 kW |
| 4.5 | 4.5 kW |
COP falls in cold weather, so a unit rated COP 4 in mild conditions may give 2–2.5 at −10 °C, raising the electrical load.
よくある質問
- How much electricity does a heat pump use?
- Divide the heat output by the COP. A 6 kW heat pump at COP 3.5 draws about 1.7 kW of electricity — roughly 7.5 A on a 230 V supply.
- What breaker does a heat pump need?
- Size it above the running current, but follow the data plate: inrush at start-up and defrost cycles often mean the maker specifies a larger breaker or a dedicated circuit.
- Why does the load change with temperature?
- COP drops as the outdoor temperature falls, so the same heat output needs more electrical input on the coldest days — exactly when demand is highest.
関連する計算機
🔥 部屋の暖房能力
部屋の暖房能力をすばやく計算します。
🏠 最大電力・主幹ブレーカー
最大電力・主幹ブレーカーをすばやく計算します。
🔌 電気料金計算機
電気料金計算機をすばやく計算します。
🔁 kVA・kW・アンペア換算
kVA・kW・アンペア換算をすばやく計算します。
すべての計算機
基礎・オームの法則
抵抗・コンデンサ
電力・配線・電源
- 📉 電圧降下計算機
- 🧵 電線サイズ計算機(AWG・mm²)
- ⚙️ 三相電力計算機
- 📐 力率改善コンデンサ計算
- 🔌 電気料金計算機
- 🔁 kVA・kW・アンペア換算
- 🔌 変圧器容量計算
- 🌀 モーター全負荷電流
- 🧰 電線管充填率
- 📊 分電盤容量計算